Laboratory Testing
    BS EN 13623:2020

    Legionella Efficacy Testing Results

    Independent UKAS-accredited laboratory testing confirms ChloroKlean Plus meets the requirements of BS EN 13623:2020 for bactericidal activity against Legionella pneumophila.

    Test Conclusion

    UKAS Accredited Laboratory

    ChloroKlean Plus at concentrations of 83ppm, 60ppm and 50ppm met the log reduction requirements as specified in EN 13623 (4 lg) with a contact time of 60 minutes for Legionella pneumophila NCTC 11192.

    Test Conditions

    Test Standard

    BS EN 13623:2020

    Test Temperature

    30°C

    Contact Time

    60 minutes

    Test Organism

    Legionella pneumophila NCTC 11192

    Additional Test Parameters

    • Interfering Substance: Yeast Extract (0.0005% final concentration)
    • Diluent: Buffered ferrous hard water
    • Neutralisation Method: Membrane Filtration using Rinsing Diluent with Sodium Thiosulphate
    • Incubation Temperature: 36°C

    Results by Concentration

    The standard requires a minimum 4 lg (log) reduction in bacterial count to pass. Results at different ChloroKlean Plus concentrations:

    83 ppm
    Log reduction: >4 lg
    Pass
    60 ppm
    Log reduction: >4 lg
    Pass
    50 ppm
    Log reduction: >4 lg
    Pass
    40 ppm
    Log reduction: <4 lg
    Partial

    About BS EN 13623:2020

    BS EN 13623:2020 is the European standard for evaluating the bactericidal activity of chemical disinfectants against Legionella in aqueous systems. It is a Phase 2, Step 1 quantitative suspension test that establishes the baseline efficacy of products under controlled laboratory conditions.

    Test Purpose

    Evaluates whether a disinfectant can achieve the required 4 log reduction against Legionella pneumophila under standardised conditions relevant to cooling water systems.

    Regulatory Relevance

    EN 13623 testing supports BPR product authorisation claims and provides evidence of efficacy for HSE compliance under HSG274 and ACOP L8 guidance.

    Practical Implications

    These laboratory results translate directly into real-world water treatment performance. The ability to achieve greater than 4-log Legionella reduction at low concentrations means that ChloroKlean Plus can maintain effective disinfection in cooling water systems while minimising chemical usage and operating costs.

    ACOP L8 Compliance

    The proven 4-log reduction supports compliance with HSE Approved Code of Practice L8 for Legionella control in evaporative cooling systems, hot and cold water systems, and other risk environments.

    HSG274 Part 1

    EN 13623 test data provides the evidence base required under HSG274 Part 1 guidance for selecting effective biocide treatments in cooling tower water management programmes.

    Ongoing Monitoring

    In practice, continuous low-level chlorine dioxide dosing (typically below 0.5 ppm) provides sustained protection. Regular monitoring with DPD test kits confirms residual levels are maintained throughout the system.

    Key Takeaway

    ChloroKlean Plus demonstrates proven efficacy against Legionella pneumophila at concentrations as low as 50ppm with a 60-minute contact time, meeting the stringent requirements of BS EN 13623:2020 for cooling water treatment applications.